Overview of Microgrid Results

Microgrid Name Generation Bus Minimum 1 hr Load (kW) Average 1 hr Load (kW) Average Daytime 1 hr Load (kW) Maximum 1 hr Load (kW) Maximum 1 hr Critical Load (kW) Existing Fossil Generation (kW) New Fossil Generation (kW) Existing Solar (kW) New Solar (kW) Existing Battery Power (kW) Existing Battery Energy Storage (kWh) New Battery Power (kW) New Battery Energy Storage (kWh) Existing Wind (kW) New Wind (kW) Total Generation on Microgrid (kW) Renewable Generation (% of Annual kWh) Emissions (Yr 1 Tons CO2) Emissions Reduction (Yr 1 % CO2) Average Outage Survived (h) O+M Costs (Yr 1 $ before tax) CapEx ($) CapEx after Tax Incentives ($) Net Present Value ($)
mg0 633 60 178 247 306 306 0 117 440 164 79 307 54 160 0 0 854 48 402 19 52 13,261 733,957 548,238 -271,091
mg1 645 25 139 215 385 160 0 37 0 509 0 0 95 219 0 0 641 47 322 48 1,773 9,615 1,267,996 868,304 -116,231
mg2 670 639 1,176 1,449 2,034 1,355 265 571 0 3,060 0 0 382 1,162 0 0 4,277 37 3,217 38 180 73,619 6,582,030 4,228,914 243,543
Summary None 789 1,492 1,911 2,713 1,821 265 725 440 3,733 79 307 531 1,541 0 0 5,772 39 3,941 37 52 96,495 8,583,983 5,645,456 -143,779

Report Generated

2024-02-01 02:19:21.820224

User Warnings

Pre-existing battery battery_634_existing will not be utilized to support loads in microgrid mg0.
Supporting critical loads across microgrids assumes an AMI metering system. If not currently installed, add budget for the creation of an AMI system.
Supporting critical loads across microgrids assumes the ability to remotely disconnect 3-phase loads.

Distribution Upgrades needed to create Microgrids

Microgrid Location Recommended Upgrade Cost Estimate ($)
mg0 mg0 Microgrid Design 100,000
mg0 mg0 Microgrid Controls 100,000
mg0 632633 SCADA disconnect switch 50,000
mg0 634a_data_center AMI disconnect meter 300
mg0 634b_radar AMI disconnect meter 300
mg0 634c_atc_tower AMI disconnect meter 300
mg1 mg1 Microgrid Design 100,000
mg1 mg1 Microgrid Controls 100,000
mg1 632645 SCADA disconnect switch 50,000
mg1 645_hangar AMI disconnect meter 300
mg1 646_office AMI disconnect meter 300
mg2 mg2 Microgrid Design 100,000
mg2 mg2 Microgrid Controls 100,000
mg2 632670 SCADA disconnect switch 50,000
mg2 684_command_center AMI disconnect meter 300
mg2 692_warehouse2 3-phase relay 20,000
mg2 675a_hospital 3-phase relay 20,000
mg2 675b_residential1 3-phase relay 20,000
mg2 675c_residential1 3-phase relay 20,000
mg2 611_runway AMI disconnect meter 300
mg2 652_residential AMI disconnect meter 300
mg2 670a_residential2 AMI disconnect meter 300
mg2 670b_residential2 AMI disconnect meter 300
mg2 670c_residential2 AMI disconnect meter 300

Description